    Abstract
    Airflow pressure losses through rigid metallic and non-metallic flexible ducts were studied and recommendations to improve the rating of flexible ducts were made as part of this study. The testing was done in compliance with ASHRAE Standard 120-1999, Methods of Testing to Determine Flow Resistance of HVAC Air Ducts and Fittings (ASHRAE 1999). Duct sizes of 6", 8", and 10" were tested in a positive pressure, blow-through configuration. An As-Built Test Protocol expands the test configurations specified by Standard 120-1999. Results of the current tests extend the existing ASHRAE/ACCA data for flexible duct which does not include pressure loss data for flexible ducts that are compressed beyond approximately 4%. The data from this study exhibit higher pressure drops than prior ACCA or ASHRAE data. Some configurations exhibit over ten times the pressure loss found in rigid duct or fully stretched flexible duct of the same diameter.
    URI
    http://hdl.handle.net/1969.1/ETD-TAMU-2011-12-10460
    Subject
    pressure losses
    ductwork
    Collections
    • Electronic Theses, Dissertations, and Records of Study (2002– )
    Citation
    Weaver, Kevin Douglas (2011). Determining Pressure Losses For Airflow In Residential Ductwork. Master's thesis, Texas A&M University. Available electronically from http : / /hdl .handle .net /1969 .1 /ETD -TAMU -2011 -12 -10460.

    DSpace software copyright © 2002-2016  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    Atmire NV
     

     

    Advanced Search

    Browse

    All of OAKTrustCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsDepartmentThis CollectionBy Issue DateAuthorsTitlesSubjectsDepartment

    My Account

    LoginRegister

    Statistics

    View Usage Statistics
    Help and Documentation

    DSpace software copyright © 2002-2016  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    Atmire NV