A Study Of Water-Cooled Air Conditioners
Abstract
Retrofitting a standard air-cooled air conditioner with a water-cooled condenser can increase the COP of the unit by 60% and increase the capacity of the unit by 40%. However, to fully realize these improvements, modification of the throttling device is necessary.
Description
Program year: 1981/1982Digitized from print original stored in HDR
Citation
Bergeron, David Joseph (1982). A Study Of Water-Cooled Air Conditioners. University Undergraduate Fellow. Available electronically from https : / /hdl .handle .net /1969 .1 /CAPSTONE -GivensJ _1986.