Show simple item record

Visit the Energy Systems Laboratory Homepage.

dc.creatorPan, S.
dc.creatorZheng, M.
dc.creatorYoshida, H.
dc.date.accessioned2010-06-04T16:25:55Z
dc.date.available2010-06-04T16:25:55Z
dc.date.issued2008-10
dc.identifier.otherESL-IC-08-10-50
dc.identifier.urihttps://hdl.handle.net/1969.1/90818
dc.description.abstractIn this paper, the environment and energy performance of an actual coupled earth tube and natural ventilation system in a gymnasium was measured during the acceptance phase in two operation states: no ventilation and natural ventilation. From the measurement result, the authors found a design fault, which the airflow temperature from floor apertures on the north side was 3 degrees lower than from the floor apertures on the south side. By the use of the CFD (Computational Fluid Dynamics) coupled analysis with natural ventilation method, the natural ventilation air volume and the indoor temperature in three outdoor air conditions have been calculated to perform commissioning. Several findings were obtained and informed to the operator.en
dc.language.isoen_US
dc.publisherEnergy Systems Laboratory (http://esl.tamu.edu)
dc.subjectEarth Tubeen
dc.subjectNatural Ventilationen
dc.subjectCFD Coupled Analysis with Natural Ventilation Methoden
dc.titleCommissioning of a Coupled Earth Tube and Natural Ventilation System at the Acceptance Phaseen
dc.typePresentationen