Energy Efficiency Evaluation of Refrigeration Technologies in Combined Cooling, Heating and Power Systems

Loading...
Thumbnail Image

Date

2006

Journal Title

Journal ISSN

Volume Title

Publisher

Energy Systems Laboratory (http://esl.tamu.edu)
Texas A&M University (http://www.tamu.edu)

Abstract

With development of absorption refrigeration technology, the cooling requirement can be met using various optional refrigeration technologies in a CCHP system, including compression refrigeration, steam double-effect absorption refrigeration, steam single-effect absorption refrigeration, flue gas absorption refrigeration and hot water absorption refrigeration, etc. As a universal criterion, the COP coefficient cannot reflect the difference in availability of driving energy for different chillers. Exergy efficiency of optional chillers in CCHP system was analyzed and compared, which can be regarded as an important reference criterion in comparison of energy efficiency. Furthermore, a new index, relative electricity saving ratio, was put forward for evaluating end energy efficiency of all kinds of chillers in a CCHP system, which indicates actual energy or electricity saving ratio for different absorption chillers with various parameters in contrast to the reference electricity-driven refrigeration scheme.

Description

Keywords

combined cooling, heating and power, energy efficiency, absorption chillers

Citation