Experimental Investigation on the Operation Performance of a Liquid Desiccant Air-conditioning System
Abstract
A large share of energy consumption is taken by an air-conditioning system. It worsens the electricity load of the power network. Therefore, more and more scholars are paying attention to research on new types of air-conditioning systems that are energy- saving and environment-friendly. A liquid desiccant air conditioning system is among them, as it has a tremendous ability for power storage and low requirements for heat resources. Heat with low temperatures, such as excess heat, waste heat, and solar power, is suitable for the liquid desiccant air-conditioning system. The feasibility and economical efficiency of the system are studied in this experimental research. The result shows that when the temperature of the regeneration is about 80?, the thermodynamic coefficient of the system is about 0.6, and the supply air temperature of the air-conditioning system remains stable at 21?, the air-conditioning system can meet human comfort levels.
Subject
liquid desiccants air-conditioning systemwaste energy applying
experiment
performance analysis
Citation
Liu, J.; Wang, J.; Wu, Z.; Gu, W.; Zhang, G. (2006). Experimental Investigation on the Operation Performance of a Liquid Desiccant Air-conditioning System. Energy Systems Laboratory (http://esl.tamu.edu); Texas A&M University (http://www.tamu.edu). Available electronically from https : / /hdl .handle .net /1969 .1 /5273.