Visit the Energy Systems Laboratory Homepage.
Energy Efficient Single Stack Exhaust Fan Systems (E3S3F)
Abstract
This paper first investigates the fan energy
performance of a constant air volume exhaust system.
Two single stack energy efficient exhaust fan systems
(E3S3F) are presented. The E3S3F-I has the static
pressure sensor located at the inlet of the exhaust
fan. It has been found to consume up to 15% less fan
power than conventional constant air volume exhaust
systems. The E3S3F-II uses a variable speed device to
maintain the static pressure at the entrance of the
stack. It consumes up to 60% less fan power than
conventional constant volume exhaust systems.
Citation
Wang, G.; Liu, M. (2001). Energy Efficient Single Stack Exhaust Fan Systems (E3S3F). Energy Systems Laboratory (http://esl.tamu.edu); Texas A&M University (http://www.tamu.edu). Available electronically from https : / /hdl .handle .net /1969 .1 /5152.