Show simple item record

Visit the Energy Systems Laboratory Homepage.

dc.creatorJoo, I.
dc.creatorLiu, M.
dc.date.accessioned2007-04-19T19:01:57Z
dc.date.available2007-04-19T19:01:57Z
dc.date.issued2002
dc.identifier.otherESL-HH-02-05-44
dc.identifier.urihttps://hdl.handle.net/1969.1/4595
dc.description.abstractThis paper provides analytical tools and engineering methods to evaluate the feasibility of the economizer for dual-duct air-handling units. The results show that the economizer decreases cooling energy consumption without heating energy penalties for dual-fan, dual-duct air-handling units. The economizer has significant heating energy penalties for single-fan, dual-duct air-handling units. The penalties are higher than the cooling energy savings when the cold airflow is less than the hot airflow. Detailed engineering analyses are required to evaluate the feasibility of the economizer for single-fan, dual-duct systems.en
dc.format.extent1099524 bytesen
dc.format.mimetypeapplication/pdf
dc.language.isoen_US
dc.publisherEnergy Systems Laboratory (http://esl.tamu.edu)
dc.publisherTexas A&M University (http://www.tamu.edu)
dc.titleEconomizer Applications in Dual-Duct Air-Handling Unitsen


This item appears in the following Collection(s)