Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power and Thermal Energy - Part 2: Case Demonstration for a Typical Climate System
Abstract
In Part 1 of this paper, the theoretical models, integrating the fan airflow, fan head, air leakage factors, are developed to analyze the impacts of the static pressure reset on both pressure dependent and pressure independent terminal boxes. In this part, a simulated air handling unit (AHU) system in Omaha NE is used to demonstrate the energy savings performance in one typical climate year. This AHU system has a static pressure reset system and two constant static pressure systems, one having pressure dependent terminal boxes and one having pressure independent terminal boxes. These simulated systems were compared mainly on the basis of fan power energy consumption and thermal energy consumption in totally a year. The example presents a good agreement with the theoretical model and simulation results. It was also shown that static pressure reset provides a promising and challenging way for the energy performance in VAV system.
Citation
Liu, M.; Zheng, K.; Wu, L.; Wang, Z.; Johnson, C. (2007). Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power and Thermal Energy - Part 2: Case Demonstration for a Typical Climate System. Energy Systems Laboratory (http://esl.tamu.edu); Texas A&M University (http://www.tamu.edu). Available electronically from https : / /hdl .handle .net /1969 .1 /6250.