Show simple item record

Visit the Energy Systems Laboratory Homepage.

dc.creatorHan, Z.
dc.creatorXia, C.
dc.creatorZhu, Y.
dc.creatorXu, G.
dc.date.accessioned2007-05-07T20:46:23Z
dc.date.available2007-05-07T20:46:23Z
dc.date.issued2006
dc.identifier.otherESL-IC-06-11-180
dc.identifier.urihttps://hdl.handle.net/1969.1/5327
dc.description.abstractCommissioning of the HVAC system has been practiced in buildings for the purpose of energy conservation and performance optimization. Commissioning of the HVAC automation system should be paid more attention. In this paper, Objective Control Method (OCM) is proposed to analyze the operational performance of VAV control system. The approach starts with the evaluation of satisfaction of indoor thermal comfort, and then is followed by the performance analysis of different control loops with a graphic chart of relations between different parameters. Finally the operation fault is detected. This approach has been applied and validated in a real VAV control system of a commercial office building in Beijing with one year's on-site measured data. By means of OCM, phenomena of 'hunting' in VAV control system are deeply studied. As a new commissioning approach of VAV control system, OCM is of great feasibility and convenience.en
dc.format.extent308962 bytesen
dc.format.mimetypeapplication/pdf
dc.language.isoen_US
dc.publisherEnergy Systems Laboratory (http://esl.tamu.edu)
dc.publisherTexas A&M University (http://www.tamu.edu)
dc.subjectVAVen
dc.subjectcommissioningen
dc.subjectOCMen
dc.subjecthuntingen
dc.titleA New Approach to Commissioning of the VAV Control Systemen


This item appears in the following Collection(s)

Show simple item record