Calculating Energy and Demand Retrofit Savings for Victoria High School: Interim Report
Abstract
As part of the LoanSTAR program, Victoria High School in Victoria, Texas underwent
two retrofits: a) an absorption chiller was changed to an electric vapor compression
chiller, and b) an EMCS system was installed after about 5 months in the post retrofit
period. Moreover, retrofit savings calculation was complex since pre-retrofit data
consisted of only monthly utility data while hourly monitored data are available for the
post-retrofit period. This report describes the method in which we have performed
retrofit energy and demand savings in Victoria High School. A previous report described
the procedure adopted when no pre-retrofit data are available. We have only used
Unnormalized Utility Bills Comparison ,or the Level-0 approach to determine electricity
(energy and demand) and gas energy savings for VHS.
Collections
Citation
Liu, Y.; Reddy, T. A.; Katipamula, S.; Claridge, D. E. (1992). Calculating Energy and Demand Retrofit Savings for Victoria High School: Interim Report. Energy Systems Laboratory (http://esl.tamu.edu), Texas A&M University; Department of Mechanical Engineering, Texas A&M University. Available electronically from https : / /hdl .handle .net /1969 .1 /2110.