Show simple item record

Visit the Energy Systems Laboratory Homepage.

dc.creatorKatipamula, S.
dc.creatorO'Neal, D. L.
dc.date.accessioned2005-07-25T20:57:34Z
dc.date.available2005-07-25T20:57:34Z
dc.date.issued1986
dc.identifier.otherTR-86-10-01
dc.identifier.urihttps://hdl.handle.net/1969.1/1975
dc.descriptionThe energy use of the Department of Health Building at Austin, Texas, was analyzed using the DOE 2.1B building energy simulation program. An analysis was made for the building as specified in the building plans and the specifications provided by the State Purchasing and General Services Commission. Operating schedules for occupancy, lighting, office equipment, and infiltration were assumed. The proposed construction of the Health building reflects improvements in energy use over buildings built several years ago (EUIs of 142 Kbtu/sf/yr compared to as much as 250 Kbtu/sf/yr). However, the energy consumption of the Health building can be reduced with certain modifications. Four options for reducing the building energy use were studies: (i) reducing the lighting levels, (ii) reducing the ventilation rate from 20 cfm/person/hr to 10 cfm/person/hr (iii) having a variable speed fan with the VAV system and economiser cycle and (iv) improved glass. These options not only reduce the peak loads but also reduce the total energy use. Finally the energy consumption of the Health building was compared with the energy consumption of the building modified to comply with the California standards.A net reduction of 44% was obtained using the California standards. The California standards are more stringent and are a better choice for state owned buildings which have a life of 30 to 40 years.en
dc.format.extent6669927 bytesen
dc.format.mimetypeapplication/pdf
dc.language.isoen_US
dc.publisherEnergy Systems Laboratory (http://esl.tamu.edu), Texas A&M University
dc.publisherDepartment of Mechanical Engineering, Texas A&M University
dc.rightsAll rights reserved by the Energy Systems Laboratory of Texas A&M and the authors.en
dc.subjectDOE-2.1Ben
dc.subjectenergy simulationen
dc.titleAn Energy and Peak Loads Analysis of the Texas Department of Health Building, Final Report, Prepared for the Energy Efficiency Division, Texas Public Utility Commissionen
dc.typeTexten