Abstract
Studies of 10 asphalt plants in the Intermountain Region have identified average ID fan energy savings of 68% by controlling airflow using Variable Frequency Drives (VFDs) on the fan motors in place of damper control (inlet or outlet). Average paybacks were 3-5 years before utility incentives.
In the 10 plants evaluated, the ID fans accounted for as much as 30% of the total plant electrical consumption. In the majority of these plants the outlet dampers were typically 50%-60% closed. Fan motors ranged from 200 Hp to 500 Hp.
With approximately 3,600 existing asphalt plants in operation across the United States, a large opportunity for retrofits exists. Working with manufacturers and owners, a new standard can be established for installing VFDs on all plants.
Anderson, G. R.; Case, P. L.; Lowery, J. (2005). Use of VFDs on Asphalt Plant Induced Draft Fans. Energy Systems Laboratory (http://esl.tamu.edu); Texas A&M University (http://www.tamu.edu). Available electronically from