Performance Analysis of Dual-Fan, Dual-Duct Constant Volume Air-Handling Units

Loading...
Thumbnail Image

Date

2001

Journal Title

Journal ISSN

Volume Title

Publisher

Energy Systems Laboratory (http://esl.tamu.edu)
Texas A&M University (http://www.tamu.edu)

Abstract

Dual-fan, dual-duct air-handling units introduce outside air directly into the cooling duct and use two variable speed devices to independently maintain the static pressure of the hot and the cold air ducts. Analytical models have been developed to compare fan power and thermal energy consumption of dualfan, dual-duct constant volume air-handling units with single-fan, dual-duct constant volume airhandling units. This study shows that the dual-fan, dual-duct system uses less fan power and less thermal energy during winter, and uses more thermal energy during summer. Thermal energy performance can be significantly improved if the thermal energy penalty can be decreased or eliminated.

Description

Keywords

Citation