Waste to Energy and Absorption Chiller: A Case Study
Abstract
All measured performance characteristics
corresponded well to manufacturer's
specifications or were within the expected range
for this type of incinerator. The simplified
economic analysis showed a payback of period 4.5
years. An optimized payback calculation based on
a set of possible improvements to the
waste-to-energy system showed a payback period of
3.8 years.