dc.description.abstractAn extensive independent evaluation recently was completed of the Multi-Source Hydronic Heat Pump (MSHHP) system, a proprietary heating, ventilating and air conditioning (HVAC) system developed by Meckler Systems Group. The MSHHP tests were conducted on a unique test bed designed and constructed by National Technical Systems (NTS) through a research and development grant program funded by Southern California Edison Company. This paper outlines testing methods and results, including evaluations of peak power and energy savings allowed by the innovative system. The main difference between the MSHHP and a conventional HVAC system is use of a chilled water "diversity" cooling loop interconnecting air to water coils (located at each water source heat pump unit) with a central chilled water storage tank. The MSHHP system uses significantly less energy than a conventional HVAC system, and lowers peak demand by shifting required electrical energy consumption to lower-cost, off-peak and mid-peak rates. Lower heat pump capacities are a main feature of the MSHHP. This is accomplished by pre-cooling return air from the zone space, a process that also allows the heat pump to operate at a higher Coefficient of Performance (COP), thereby contributing to further energy savings.en
dc.publisherEnergy Systems Laboratory (http://esl.tamu.edu)
dc.publisherTexas A&M University (http://www.tamu.edu)
dc.titleMulti-Source Hydronic Heat Pump System Performance Test Beden
dc.contributor.sponsorThe Mackler Group


This item appears in the following Collection(s)

Show simple item record