Visit the Energy Systems Laboratory Homepage.
dc.creator | Haberl, J. S. | |
dc.creator | Bou-Saada, T. E. | |
dc.creator | Saman, N. F. | |
dc.date.accessioned | 2005-07-25T20:59:06Z | |
dc.date.available | 2005-07-25T20:59:06Z | |
dc.date.issued | 2001 | |
dc.identifier.other | TR-01-02-02 | |
dc.identifier.uri | https://hdl.handle.net/1969.1/2011 | |
dc.description | These calculations were developed as part of the ASHRAE 865-RP project, and include tables that list the results for the 865-RP accuracy tests, as well as the test conditions. These spreadsheets are also useful for developing educational materials, and can be used to check the values obtained from a computer simulation program that contain the exact same schematic as is shown for each system. With only a few exceptions, the formulas for the calculations have come from the ASHRAE Handbook, as indicated in the spreadsheet narrative. These spreadsheets were developed in the most basic Lotus *.wk1 format and can be run in any spreadsheet that accepts Lotus *.wk1 format. To use the spreadsheets the user loads the spreadsheet, updates only the values needed and recalculates the spreadsheet manually (i.e., press the F9 button). Calculations are repeated column-wise in the spreadsheet to reach convergence. Each calculation represents one set of conditions. To obtain answers for multiple conditions the user will need to enter the new conditions and recalculate for each set of conditions. | en |
dc.description.abstract | This report contains engineering calculations for seven (7) air-side, heating, ventilating and air conditioning systems (HVAC) systems, including: dual duct constant volume (DDCAV), dual duct variable volume (DDVAV), constant volume with reheat (CAVRH), and variable volume with reheat (VAVRH), four pipe fan coil unit (FC), four pipe induction unit (FI), and a single zone air conditioning system (SZ). These calculations are presented in spreadsheets that include a running commentary so that the reader can trace through the calculations to see what is being performed. Each system also contains a one-line diagram that shows the system being simulated and the location of the variables used in the calculation. | en |
dc.format.extent | 266313 bytes | en |
dc.format.mimetype | application/pdf | |
dc.language.iso | en_US | |
dc.publisher | Energy Systems Laboratory (http://esl.tamu.edu), Texas A&M University | |
dc.rights | All rights reserved by the Energy Systems Laboratory of Texas A&M and the authors. | en |
dc.subject | HVAC | en |
dc.subject | ASHRAE 865-RP | en |
dc.subject | Lotus | en |
dc.title | Air-Side Energy Use Calculations for Four HVAC Systems: Dual Duct Constant Volume (DDCAV), Dual Duct Variable Volume (DDVAV), Constant Volume with Reheat (CAVRH), Variable Volume with Reheat (VAVRH), Four Pipe Fan Coil Unit (FC), Four Pipe Induction Unit (FI), and Single Zone (SZ) Systems, Revised June 2002 | en |
dc.type | Text | en |
This item appears in the following Collection(s)
-
Technical Reports
Technical Reports from the Energy Systems Laboratory